MTD 464 Betriebsanleitung Seite 331

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 493
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 330
(a)
(b)
(c)
(d)
ARMY TM 9-6115-464-34
AIR FORCE TO 35C2-3-445-2
NAVY NAVFAC P-8-624-34
With chassis cover (4, figure 3-130) removed, connect positive lead of voltmeter to heat sink where
CR1-CR3 are mounted. Connect negative lead to heat sink where CR4-CR6 are mounted. (See
item 17, figure 3–130).
Apply 12 Vac (any frequency between 50 and 400 Hz) to pins A and B of connector J13.
Voltmeter connected across heat sinks should indicate 9.3 Vdc.
Remove 12 Vac from pins A and B and connect to E and F, then to J and K. In each case, voltmeter
should indicate 9.3 Vdc.
(4) If the requirements of any test are not met, check components using figure 3-131 or 3-132 and table
3-8 as a guide to locate the malfunction. Correct before installing the static exciter and voltage
regulator assembly.
g. Installation.
(1) Position static exciter and voltage regulator to install Iockwasher (2, figure 3-130) and screws (1).
(2) Connect electrical connectors to static exicter and voltage regulator.
3-93. RELAY TABLE COMPONENTS ADJUSTMENTS.
a. General.
After maintenance has been performed on any of the relay table components, the appropriate
adjustments shall be performed.
b. Voltage
Adjustment.
(1) Position voltage adjustment rheostat R2 on generator set control cubicle to the approximate
midpoint.
(2) Refer to the Operator and Unit Maintenance Manual and start the generator set.
(3) Adjust voltage rheostat R2 to obtain generator assembly rated voltage at generator set load terminal
board.
c. Paralleling Adjustments.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
Refer to the Operator and Unit Maintenance Manual and connect a rated load to the generator set
load terminal board.
Start the generator set and operate at full rated load.
Install the shorting plug in the paralleling receptacle.
Place the operations switch on the generator set control cubicle in the PARALLEL position.
Adjust reactive current adjust potentiometer R29 of the special relay assembly to provide a special
droop of 3 percent.
Adjust the load sharing adjust rheostat (R28) of the precise relay assembly until 4 to 6 VDC appear
across pins A and B of the paralleling receptacle. Insure that the positive lead of the meter is
connected to pin A. Repeat same procedure for all other generator sets to be paralleled. Voltage
readings must be identical on all generator sets to be paralleled to insure load sharing. Failure to
make this adjustment will result in load rejection and/or safety system shutdown.
NOTE
Step (6) pertains to precise generator sets only.
Refer to the Operator and Unit Maintenance Manual and shut down the generator set.
3-277
Seitenansicht 330
1 2 ... 326 327 328 329 330 331 332 333 334 335 336 ... 492 493

Kommentare zu diesen Handbüchern

Keine Kommentare