Sensitivity
A heat sensor with class.
The heat sensor can be configured
for the standard classes A1, A2 and B in
accordance with EN 54-5, and for special
areas of application also with the index R
or S in accordance with EN 54-5. Three
standard classes in combination with the
index R or S give nine different options
for optimal adaptation to environmental
conditions.
Operational security assured
by self-tests.
The MTD 533X checks its own ability
to function properly. It constantly checks
itself, while monitoring all operating
parameters and reports contamination,
short circuits and other faults as
required. The MTD 533X carries this
self-test out once a second. Even in a
disabled state, it is also ready for use and
to sound the alarm. If it sends an alarm
from this state to the fire alarm control
panel, then it will only be used for the
execution of measures relating to the
formation of fire zones, e.g. closing fire
prevention doors, and no unnecessary
alarm will be sent to the fire brigade in
this instance.
Interactive communication
with the fire alarm control panel.
The MTD 533X communicates
intensively with the control panel and
reports to it even the smallest deviation
from the normal state. With its
intelligent decision-making logic the
MTD 533X connects smoke and
temperature signals, and is therefore sure
to only report actual fires. As soon as
the predefined signalling values are
exceeded, then the alarm is triggered.
If required a pre-alarm can also be
programmed.
90°
18 0°
0°
270°
Response characteristics
Innovative CUBUS levelling.
The MTD 533X uses a unique specially
developed technology: CUBUS levelling.
The detector constantly monitors its
surrounding conditions with regard to
the absolute maximum temperature as
well as the relative increase in
temperature per minute and from these
factors calculates the relevant sensitivity
to smoke and temperature for wherever it
is deployed. In this way, the sensitivity
of the smoke sensor permanently adapts
automatically and dynamically to the
surrounding environmental conditions.
If the temperature exceeds the absolute
or relative values, then the smoke
chamber’s sensitivity is also automatically
adapted accordingly. The detector is now
more alert as to whether traces of visible
or invisible smoke particles can be
detected. If the temperature falls again,
then the sensitivity of the smoke sensor
also decreases.
Designed for optimized detection.
Using the most up-to-date computer-
assisted methods and as a result of more
than 800 fire tests the flow behaviour has
been optimized to such an extent that,
even under extreme conditions – e.g. the
formation of heats below the ceiling as a
consequence of high external
temperatures, a quick and completely
safe detection can be guaranteed.
Optimized smoke penetration and the
balance temperature symmetry guarantee
that the MTD 533X is able to
distinguish between deceptive levels and
an emergency.