MI 020-460October 1996InstructionRTT20 I/A Series® Temperature Transmitter Operation, Configuration, and Calibration Using a HART Communicator
MI 020-460 – October 1996 Configuration 6Figure 5. Online Configuration Flowchart (Continued)7. Transmitter Info1. Message2. Xmtr Assembly3. Device I
Configuration MI 020-460 – October 1996 7Explanation of ParametersMeasuring Point Config Sensor Config Output Failure HandlingSpecify the Sensor Faul
MI 020-460 – October 1996 Calibration 8Options CalibrationThe RTT20 Transmitter has an advanced self-calibration routine that greatly extends the time
Calibration MI 020-460 – October 1996 9Custom Curve CalibrationYour transmitter may be calibrated to a standard or custom curve using the Communicato
MI 020-460 – October 1996 Calibration.ISSUE DATES OCT 1996Vertical lines to right of text or illustrations indicate areas changed at last issue date
MI 020-460 – October 1996
iiiContentsGeneral Description ...1Reference
MI 020-460 – October 1996 Contents iv
1IntroductionGeneral DescriptionThe RTT20-T Temperature Transmitter with HART communications may be configured, operated, and calibrated using the HAR
MI 020-460 – October 1996 Introduction 2Figure 2. RTT20 Temperature Transmitter Top Level Online MenuConnecting the Communicator to the TransmitterCo
Operation MI 020-460 – October 1996 3OperationTo display the measurement (Process Variable or PV) on the Communicator, select 2. Online from the Main
MI 020-460 – October 1996 Configuration 4Online Configuration FlowchartsFigure 3. Online Configuration Flowchart1. Measuring Point2. Config Sensor1.
Configuration MI 020-460 – October 1996 5Figure 4. Online Configuration Flowchart (Continued)Continued from Figure 33. Config Output4. Failure Handl